Trade Skill Passport
← All modules
A2

Lockout/Tagout & Absence-of-Voltage Verification

309A Construction & Maintenance Electrician · Category: Safety · Stamp freshness: 2 years · Standard duration: 15 minutes

The safety gatekeeper module: a complete lockout/tagout and prove-dead sequence on a training panel, performed and narrated in one take.

The task

On a training distribution panel or disconnect, complete a full lockout sequence: notify, isolate, lock and tag, prove your tester on a known live source, test every point for absence of voltage, do a short simulated work step with the lock in place, then restore power in the correct order.

Performed on a practice board or training panel and recorded in one continuous take with your attempt's dynamic passcode — see the rules centre for the recording rules that apply to every module.

Required steps

  1. Announce the work: state which equipment will be de-energized and what it affects.
  2. Open the disconnect/breaker and fit your personal lock and tag (name, date, task).
  3. Prove the tester: verify it works on a known live simulated source or test point.
  4. Test every point (L1, L2, L3 or L–N), narrating each reading out loud.
  5. Perform the simulated work step with the lock still in place.
  6. Restore: account for tools and people, remove tag and lock, re-energize, and confirm out loud.

Safety veto points

Any one of these fails the attempt outright, whatever the total score.

  • Working without a lock applied
  • Skipping the tester self-check (prove–test–prove)
  • Skipping any test point
  • Lock or tag missing the name or date
  • Removing the lock during the work step

What the assessor checks

  • All steps present, in the safe order
  • Tester proved before and readings narrated
  • Lock stays on for the whole work step

Graded on the five-dimension rubric — Quality 40 · Safety 25 · Craftsmanship 15 · Speed 10 · Preparation 10. Levels: L3 ≥ 90 with Quality ≥ 90 · L2 ≥ 75 · L1 ≥ 60.

What you need

  • Training panel with a simulated supply indicator and a known-live test point
  • Personal lockout lock and tag
  • Voltage tester (contact or non-contact, must be demonstrated in a self-check)
  • Marker

Ready when you are.

Pass the Common Core once, apply for A2, pass its short theory exam, and record your practical. Basic DIY verification is free.

Apply for A2Other modules